H: Terminal Functions
◆
H1: Digital Inputs
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H1-01
(0438)
Terminal S1 Function
Selection
Sets the function for MFDI terminal S1.
Note:
The default setting is
F
when you initialize the drive for
3-Wire Initialization [A1-03 =
3330]
.
40
(1 - 1FF)
H1-02
(0439)
Terminal S2 Function
Selection
Sets the function for MFDI terminal S2.
Note:
The default setting is
F
when you initialize the drive for
3-Wire Initialization [A1-03 =
3330]
.
F
(1 - 1FF)
H1-03
(0400)
Terminal S3 Function
Selection
Sets the function for MFDI terminal S3.
24
(0 - 1FF)
H1-04
(0401)
Terminal S4 Function
Selection
Sets the function for MFDI terminal S4.
14
(0 - 1FF)
H1-05
(0402)
Terminal S5 Function
Selection
Sets the function for MFDI terminal S5.
Note:
The default setting is
0
when the drive is initialized for
3-Wire Initialization [A1-03 =
3330]
.
3
(0 - 1FF)
H1-06
(0403)
Terminal S6 Function
Selection
Sets the function for MFDI terminal S6.
Note:
The default setting is
3
when the drive is initialized for
3-Wire Initialization [A1-03 =
3330]
.
4
(0 - 1FF)
H1-07
(0404)
Terminal S7 Function
Selection
Sets the function for MFDI terminal S7.
Note:
The default setting is
4
when the drive is initialized for
3-Wire Initialization [A1-03 =
3330]
.
6
(0 - 1FF)
H1-40
(0B54)
Mbus Reg 15C0h bit0
Input Func
Sets the MFDI function assigned to
bit 0
of the MEMOBUS register
15C0 (Hex.)
.
F
(1 - 1FF)
H1-41
(0B55)
Mbus Reg 15C0h bit1
Input Func
Sets the MFDI function assigned to
bit 1
of the MEMOBUS register
15C0 (Hex.)
.
F
(1 - 1FF)
H1-42
(0B56)
Mbus Reg 15C0h bit2
Input Func
Sets the MFDI function assigned to
bit 2
of the MEMOBUS register
15C0 (Hex.)
.
F
(1 - 1FF)
H1-61
(39E1)
RUN
Terminal S1 On-Delay
Time
Sets the length of time necessary for Terminal S1 to be closed before the drive does the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-62
(39E2)
RUN
Terminal S2 On-Delay
Time
Sets the length of time necessary for Terminal S2 to be closed before the drive does the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-63
(39E3)
RUN
Terminal S3 On-Delay
Time
Sets the length of time necessary for Terminal S3 to be closed before the drive does the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-64
(39E4)
RUN
Terminal S4 On-Delay
Time
Sets the length of time necessary for Terminal S4 to be closed before the drive does the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-65
(39E5)
RUN
Terminal S5 On-Delay
Time
Sets the length of time necessary for Terminal S5 to be closed before the drive does the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-66
(39E6)
RUN
Terminal S6 On-Delay
Time
Sets the length of time necessary for Terminal S6 to be closed before the drive does the
programmed function.
0.00 s
(0.00 - 300.00 s)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV