584
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
Figure 4.20 Standard Drive Connection Diagram
*1
Set the wiring sequence to de-energize the drive with the fault relay output. If the drive outputs a fault during fault restart when you use
the fault restart function, set
L5-02 = 1 [Fault Contact at Restart Select = Always Active]
to de-energize the drive. Be careful when you
use a cut-off sequence. The default setting for
L5-02
is
0 [Active Only when Not Restarting]
.
*2
Use branch circuit protection devices as recommended in this manual.
*3
Cooling fan wiring is not necessary for self-cooling motors.
*4
Connect DC power supply input to terminals - and +1.
WARNING!
Fire Hazard. Only connect factory-recommended devices or circuits to drive terminals - and +1. Do not connect
AC power to these terminals. Incorrect wiring can cause damage to the drive and serious injury or death from fire.