YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
371
L5-04:
U1-02:
Figure 2.94 Time Chart for Early Cancellation of Auto-Restart Function
1 : Always Active
The drive always activates fault output.
■
L5-04: Interval Method Restart Time
No.
(Hex.)
Name
Description
Default
(Range)
L5-04
(046C)
Interval Method Restart
Time
Sets the time interval between each Auto Restart attempt.
10.0 s
(0.5 - 3600.0 s)
■
L5-07: Fault Reset Enable Select Grp1
No.
(Hex.)
Name
Description
Default
(Range)
L5-07
(0B2A)
Fault Reset Enable Select
Grp1
Use these 4 digits to set the Auto Restart function for
oL1
to
oL4
. From left to right, the digits set
oL1
,
oL2
,
oL3
, and
oL4
, in order.
1111
(0000 - 1111)
0000 : Disabled
0001 : Enabled (—/—/—/oL4)
0010 : Enabled (—/—/oL3/—)
0011 : Enabled (—/—/oL3/oL4)
0100 : Enabled (—/oL2/—/—)
0101 : Enabled (—/oL2/—/oL4)
0110 : Enabled (—/oL2/oL3/—)
0111 : Enabled (—/oL2/oL3/oL4)
1000 : Enabled (oL1/—/—/—)
1001 : Enabled (oL1/—/—/oL4)
1010 : Enabled (oL1/—/oL3/—)
1011 : Enabled (oL1/—/oL3/oL4)
1100 : Enabled (oL1/oL2/—/—)
1101 : Enabled (oL1/oL2/—/oL4)
1110 : Enabled (oL1/oL2/oL3/—)
1111 : Enabled (oL1/oL2/oL3/oL4)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV