H2-66: Term M5-M6 Secondary Function
No.
(Hex.)
Name
Description
Default
(Range)
H2-66
(1B4C)
Expert
Term M5-M6 Secondary
Function
Sets the second function for terminal M5-M6. Outputs the logical calculation results of the terminals
assigned to functions by
H2-03 [Terminal M5-M6 Function Select]
.
F
(0 - FF)
■
H2-67: Terminal M5-M6 Logical Operation
No.
(Hex.)
Name
Description
Default
(Range)
H2-67
(1B4D)
Expert
Terminal M5-M6 Logical
Operation
Sets the logical operation for the functions set in
H2-03 [Term M5-M6 Function Selection]
and
H2-
66 [Term M5-M6 Secondary Function]
.
0
(0 - 8)
Note:
Refer to
Output of Logical Operation Results of MFDO on page 304
for more information about the relation between parameter settings and
logical operations.
■
H2-68: Terminal M5-M6 Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-68
(1B4E)
Expert
Terminal M5-M6 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal M5-M6.
0.1 s
(0.0 - 25.0 s)
◆
MFDO Setting Values
Selects the function configured to MFDO.
■
0: During Run
Setting Value
Function
Description
0
During Run
The terminal activates when you input a Run command and when the drive is outputting voltage.
Figure 2.59 Drive Running Time Chart
ON : Drive is running
The drive is receiving a Run command or outputting voltage.
OFF : Drive is stopping
■
1: Zero Speed
Setting Value
Function
Description
1
Zero Speed
The terminal activates when the output frequency <
E1-09 [Minimum Output Frequency]
.
Note:
Parameter
E1-09
is the reference in all control methods.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV