CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
93
P043
0 to 6553.5
Time Enabled
[ - ]
0.1h
Indicates the total number of hours that the Soft-Starter has run.
This value remains stored even when the Soft-Starter is turned OFF.
Indicates up to 6553,5 hours, rolls over to 0000.
If P204 is set to 3, P043 is reset to zero.
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Indicates the total number of hours that the Soft-Starter was powe-
red.
This value remains stored even when the Soft-Starter is switched
OFF.
NOTE!
The indication on the LED display was modified and is different
from the previous software versions, following now the standard
described in the item 4.1.
P042
0 to 65535
Time Powered
[ - ]
1h
Indicates the energy consumed by the motor, in kWh.
Indicates up to 999.9kWh, then it return
s
to zero.
If P204 is set to 3, P044 is reset to zero.
This value remains stored even when the
Soft-Starter is turned OFF.
Indicates the energy consumed by the motor, in MWh.
Indicates up to 9999MWh, then it returns to zero.
If P204 is set to 3, P045 is reset to zero.
This value remains stored even when the
Soft-Starter is turned
OFF.
P044
0 to 999.9
kWh Counter
[ - ]
1kWh
P045
0 to 9999
MWh Counter
[ - ]
1MWh
It stores the value of the maximum current during the start.
The value of P047 is reset at the beginning of each start.
If P204 is set to 3, P047 is reset to zero.
This value is not kept when the Soft-Starter is turned OFF.
It does not record currents of the JOG function.
It stores the value of the average current during the start.
The value of P048 is reset at the beginning of each start.
P204 is set to 3, P048 is reset to zero.
This value is not kept when the Soft-Starter is turned OFF.
It does not record currents of the JOG function.
P047
0 to 9999.9
Maximum Starting
[ - ]
Current 0.1A
P048
0 to 9999.9
Average Starting
[ - ]
Current 0.1A
It stores the real starting time.
The real starting time is the time required for the motor to reach its
nominal speed.
The real starting time depends on the starting parameters settings
and on the load conditions. The time set in P102, even for voltage
ramp, is not the real starting time. A motor without load, for instance,
P049
0 to 999
Real Starting Time
[ - ]
1s