![WEG SSW06 User Manual Download Page 167](http://html.mh-extra.com/html/weg/ssw06/ssw06_user-manual_950614167.webp)
CHAPTER 8 - DIAGNOSTICS AND TROUBLESHOOTING
167
FAULT
E70
Undervoltage at the
electronics supply
E71
Internal By-pass relay
contact is open
E72
Overcurrent before
By-pass closing
E74
Current imbalance
E75
Line frequency out of
range
E76
Undercurrent before
By-pass closing
E77
By-pass relay contact
is closed
E78 or A78
Undertorque
E79 or A79
Overtorque
E80 or A80
Underpower
DESCRIPTION OF THE ACTUATION
When the supply of the control board power
supply is lower than 93,5Vac.
When any problem with the contacts of the
By-pass relay, internal or external, has been
detected at full voltage after start.
When at the end of the acceleration ramp
the current is not lower than 2x the nominal
current of the Soft-Starter (P295x2) before
closing of the internal By-pass relay.
When the current of one of the phases is
lower or higher than the programmed value
during the programmed time.
The other motor phases are used as refe-
rence.
When the frequency is lower or higher than
the limits from 42.5Hz to 69Hz for more than
0.5s.
When at the end of the acceleration ramp
the current is lower than 0.1x the nominal
current of the Soft-Starter (P295x0.1) before
closing of the By-pass relay.
When the contact of the By-pass relay, internal
or external, will not open.
When the value of the torque is lower than
the programmed value, longer than the pro-
grammed time. Referenced to the nominal
motor torque.
When the value of the torque is higher than
the programmed value, longer than the pro-
grammed time. Referenced to the nominal
motor torque.
When the value of the active power is lower
than the programmed value, longer than the
programmed time. Referenced to the nominal
motor power.
POSSIBLE CAUSES
Phase loss in the control board supply.
Loose contact in the control board supply.
Fuse in control board supply is open, glass fuse
5x20mm 2A with delayed action.
Loose contact of the internal or extenal By-pass
relay supply.
Loose contact of the internal or extenal By-pass relay
due to an overload.
P140=1 without external By-pass relay connected.
Nominal Soft-Starter current has been wrong
programmed at P295.
Nominal Soft-Starter current has been wrong pro-
grammed at P295.
The time programmed at P102 is shorter than
required for the motor start by voltage ramp.
Nominal motor current is higher than allowed for
the Soft-Starter.
Stalled motor, locked rotor.
The value of the current imbalance between
phases (in percentage of P401) is higher than
the programmed in P614, longer than the time
programmed in P615.
Voltage drop in one or more phases of the power
supply.
Phase loss in the power supply.
Input transformers have been undersized.
Input fuses are open.
Loose contact of the power supply connections or
connections to the motor.
When the Soft-S motor are being supplied
by a generator that is unable to drive the motor at
rated load or is unable to start the motor.
Power supply fault or thyristor fault before By-pass
closing.
The nominal Soft-Starter current has been wrong
programmed at P295.
Nominal motor current is lower than the minimum
current (P295x0.1).
For tests you can set P616=0.
Loose contact of the internal or extenal By-pass
relay supply.
Loose contact of the internal or external By-pass relay
due to an overload.
Short circuit in parallel with the contact of By-pass:
thyristor in short circuit, external short circuit.
For multimotors applications you can set P621=0.
The percentage value programmed as maximum
acceptable Undertorque limit (P650) is below the
necessary for the motor and the application. In appli-
cations with hydraulic pump, it may be running empty.
The percentage value programmed as maximum
acceptable Overtorque limit (P652) is below the
necessary for the motor and the application. Tran-
sitory excess of load at the motor. Locked motor,
blocked rotor.
The percentage value programmed as maximum
acceptable Underpower limit (P660) is below the
necessary for the motor and the application. In appli-
cations with hydraulic pump, it may be running empty.
RESET
Power-on
Manual Reset
Auto-reset
DIx
Power-on
Manual Reset
DIx
Power-on
Manual Reset
DIx
Power-on
Manual Reset
Auto-reset
DIx
Power-on
Manual Reset
DIx
Power-on
Manual Reset
DIx
Power-on
Manual Reset
DIx
Power-on
Manual Reset
Auto-reset
DIx
Power-on
Manual Reset
Auto-reset DIx
Power-on
Manual Reset
Auto-reset DIx
Table 8.1 (Cont.)
- Detailed fault description
Summary of Contents for SSW06
Page 2: ......