CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
92
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Indicates the software version contained in the microcontroller me-
mory of the control board.
P023
X.XX
Software Version
[ - ]
-
P020
0 to 99
Current Fault
[ - ]
-
It indicates if any fault is active.
NOTE!
Erros related to communication (E28, E29 and E30) are not
indicated in P020.
P021
0 to 99
Current Alarm
[ - ]
-
It indicates if any alarm is active.
It indicates the analog output AO1 value directly in “mV”.
P027
0 to 10.000
Analog Output AO1
[ - ]
Value 0.001V
It indicates the analog output AO2 value directly in “mA”.
P028
0 to 20.000
Analog Output AO2
or
Value
4.000 to 20.000
[ - ]
0.001mA
Accuracy: ± 2% for full scale (full scale is 5 x In of the SSW-06).
NOTE!
When the inside delta connection of the motor is used (P150=1),
the indication of the current value will already be multiplied by
1.73.
P030
0 to 9999.9
Current of Phase R
[ - ]
0.1A
P031
0 to 9999.9
Current of Phase S
[ - ]
0.1A
P032
0 to 9999.9
Current of Phase T
[ - ]
0.1A
P033
0 to 999
Line Voltage - R-S
[ - ]
1V
P034
0 to 999
Line Voltage - S-T
[ - ]
1V
P035
0 to 999
Line Voltage - T-R
[ - ]
1V
Accuracy: ± 2V.
NOTE!
The voltage will only be indicated when it reaches a value gre-
ater than 15V. Below this value, only 0 (zero) will be indicated.