CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
129
Range
[Factory Setting]
Parameter
Unit
Description / Notes
The undercurrent and the overcurrent parameters are set as per-
centage of the nominal motor current (P401).
P610 sets the immediate undercurrent level at which the motor can
operate without problems during the time adjusted in P611. After this
time has elapsed the Soft-Starter is disabled indicating undercurrent
fault. This function is generally used in applications with hydraulic
pumps which cannot be operated without a load.
P612 sets the maximum overcurrent levels that the motor or Soft-
-Starter allows for the time set at P613, after which the Soft-Starter
is switched Off and the Overcurrent Error is displayed.
For programming examples refer to the item 7.2.2.
NOTE!
These Functions are only active after the motor start and after
full voltage level has been reached.
P610
(1)
0 to 99
Immediate
[ 20 ]
Undercurrent
1%In of the Motor
P611
(1)
0 to 99
Immediate
[ 0=Inactive ]
Undercurrent Time
1s
P612
(1)
0 to 99
Immediate
[ 20 ]
Overcurrent
1%In of the Motor
P613
(1)
0 to 99
Immediate
[ 0=Inactive ]
Overcurrent
1s
Time
Figure 6.24
- Actuation Levels for Overcurrent and Undercurrent
I(A)
0
P610
P612
Start
Nominal
Disable
Enable
Actuation Region
t(s)
I(A)
t
P610
P612
t(s)
Nominal
Fault Action
Fault Action
I(A)
Nominal
t(s)
t
P611
P613
Undercurrent
Overcurrent
The current imbalance values are set as percentage of the nominal
motor current (P401).
P614 sets the maximum current difference between the three motor
phases at which the motor can operate without problems, for the
time set at P615. If these values are exceeded, the Soft-Starter is
switched Off and the Current Imbalance error is displayed.
These settings also activate the phase fault protection during the
starting process and during operation at full voltage.
NOTE!
This function is actuated only after motor start and after full
voltage level has been reached.
P614
(1)
0 to 30
Current Imbalance
[ 15 ]
between Phases
1 %In of the Motor
P615
(1)
0 to 99
Current Imbalance
[ 1 ]
between 1s
Phases Time