CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
118
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P295
(1)(2)
0 to 20
SSW Nominal
[ According to the
Current
nominal current
of the Soft-Starter
SSW-06 ]
-
Table 6.31
- Functions of the Relay Outputs
RLx Parameter P277 P278 P279
Function
(RL1) (RL2) (RL3)
Not Used
0
0
0, 4
Running
1 1 1
Full Voltage
2
2
2
External By-pass
3
3
3
FWD/REV-K1 4 - -
FWD/REV-K2 - 4 -
DC-Braking 5 5 5
No Fault
6
6
6
Fault
7 7 7
Fieldbus
8 8 8
Serial
9
9 9
SoftPLC
10
10
10
No Alarm
11
11
11
Alarm
12 12 12
Breaker Shunt Trip 13 13 13
must be enabled with forward motor direction of rotation. See P231
and the recommended setup at items 3.3 and 3.3.8.
“FWD/REV-K2”
= this operation is similar to the “Running”, but it
must be enabled with reverse motor direction of rotation. See P231
and the recommended setup at items 3.3 and 3.3.8.
“DC-Braking”
= the output will be enabled while the DC-Braking
is active. See P500 and the recommended setup at items 3.3 and
3.3.11.
“No Fault”
= the output is enabled, if the Soft-Starter SSW-06 is
not disabled due to any error.
“Fault”
= the output is enabled, if the Soft-Starter SSW-06 is disa-
bled due to any error.
“Fieldbus”
= it makes it possible for the master of a Fieldbus commu-
nication network to control the digital output. Refer to the Fieldbus
communication manual for more details.
“Serial”
= it makes it possible for the master of a serial commu-
nication network to control the digital output. Refer to the serial
communication manual for more details.
“SoftPLC”
= it allows the SoftPLC to control the digital output. Refer
to the WLP Software manual for more details.
“No Alarm”
= the output is enabled, if the Soft-Starter SSW-06 is
not disabled due to any alarm.
“Alarm”
= the output is enabled, if the Soft-Starter SSW-06 is disa-
bled due to any alarm.
“Breaker Shunt Trip” =
Error Group - When one of the following
errors occur: E11, E15, E18, E19, E41, E77, the output is activated.
The tripping of any of these protections may indicate that the SSW-
06 has a short circuit in the power circuit, thyristors or by-pass. They
can be used to open the power isolation circuit breaker (Q1) (Item
3.3).
Table 6.32
- Nominal current configuration
P295 Nominal
Current
P295 Nominal
Current
P295 Nominal
Current
0
10A
8
170A
16
670A
1
16A
9
205A
17
820A
2
23A
10
255A
18
950A
3
30A
11
312A
19
1100A
4
45A
12
365A
20
1400A
5
60A
13
412A
21
1000A
6
85A
14
480A
22
1300A
7
130A
15
604A