CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
115
Range
[Factory Setting]
Parameter
Unit
Description / Notes
It selects the signal type of the current analog output AO2.
P255
0 to 1
AO2 Analog Output
[ 0=0-20mA ]
Type (0 to 20)mA or
-
(4 to 20)mA
P255
AO2 Output Type
0
(0 to 20)mA
1
(4 to 20)mA
For transforming the current analog output AO2 to a voltage output
of 0 to 10V, connect a resistor of 500
Ω
± 1% 0.5W in parallel with
the output signal.
Remember when the output type is selected to (4 to 20)mA, this will
be the total range of the signal output.
0% of the signal = 4mA and 100% of the signal = 20mA.
Table 6.28
- AO2 signal type
Scale of the Analog Output indications:
- Full scale =10V: for Output AO1.
- Full scale =20mA for Output AO2.
Current (%In of the SSW)
Input Voltage (%Un of the SSW)
Output Voltage (%Un of the SSW)
Power Factor
Motor Thermal Protection
Power (W)
Power (VA)
Torque (% Tn Motor)
Fieldbus
Serial
SoftPLC
P251
P253
Gain
P252, P254
AO1
AO2
Figure 6.15
- Block diagram of the Analog Outputs
Table 6.29
- Functions of the Analog Outputs
P251/P253 Function of the Analog Output
Full Scale When
0
Not used
-
1
Current in % In of the SSW
5 x P295
2
Input Voltage in % Un of the SSW 1.5 x P296(max.)
3
Motor Voltage in % Un of the SSW 1.5 x P296(max.)
4
Power Factor
P008 = 1.00
5
Thermal Protection
P050 = 250%
6
Power in W
1.5 x
√
3 x P295 x P296(max.)
7
Power in VA
1.5 x
√
3 x P295 x P296(max.)
8
Torque in % Tn of the Motor
5 x P009 = 100%
9
Fieldbus
16383 (3FFFh)
10
Serial
16383 (3FFFh)
11
SoftPLC
16383 (3FFFh)