CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
140
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P674
Motor Overtemperature
Alarm Reset Level Ch1
P678
Motor Overtemperature
Alarm Reset Level Ch2
P682
Motor Overtemperature
Alarm Reset Level Ch3
P686
Motor Overtemperature
Alarm Reset Level Ch4
P690
Motor Overtemperature
Alarm Reset Level Ch5
0 to 250
[ 108 ]
ºC
NOTE!
The value programmed for motor overtemperature alarm reset
must be lower that the value programmed for alarm actuation
level.
It programs the level of motor overtemperature alarm reset.
Normally a value 30% below of the insulation class of the motor
is used.
If the motor overtemperature alarm is active and the motor
temperatura value is lower than the reset level, the indication of
the alarm will be removed.
P691
PT100 Sensors Fault
(Ch1 to Ch5)
0 to 2
[ 0=Inactive ]
-
It programs the way of functioning of the verification of problems
in the temperature sensors. This function detects sensor in short
circuit or with broken cable.
In case of problem in some temperature sensor, if P691 is pro-
grammed for error, the motor will be turn off and will be indicated
the error message in the HMI. In case that it is programmed for
alarm, the motor continues running and will be indicated the mes-
sage of alarm in the display of the HMI.
Table 6.53
- Fault sensor action selection
It allows selecting the protection trip between Fault and Alarm.
The Fault trips disabling the motor when the thermal protection
reaches the maximum level (250%). It only leaves this condition
through the Reset. This condition can be indicated via digital output.
P705
Motor Thermal Pro-
tection Trip
0 to 2
[ 0=Fault E05 ]
1
Table 6.54
- Selection between fault and alarm of the motor thermal protection
6.8 SELECTION BETWEEN FAULT AND ALARM - P700 to P790
P691
Description
0
Inactive
1
Error E43 to E52
2
Alarm A43 to A52
P705
Description
0
Fault E05
1
Alarm A05
2
Fault and alarm
Summary of Contents for SSW06