CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
139
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P672
Motor Overtemperature
Error Actuation Level
Ch 1
P676
Motor Overtemperature
Error Actuation Level
Ch 2
P680
Motor Overtemperature
Error Actuation Level
Ch 3
P684
Motor Overtemperature
Error Actuation Level
Ch 4
P688
Motor Overtemperature
Error Actuation Level
Ch 5
0 to 250
[ 139 ]
ºC
It programs the maximum level of temperature that the motor can
operate without problems. Normally a value 10% below of the
insulation class of the motor is used.
If the motor temperature exceed the programmed level and the
corresponding channel is programmed for error, the motor will
be turn off and will be indicated error message in the display of
the HMI.
P673
Motor Overtemperature
Alarm Actuation Level
Ch1
P677
Motor Overtemperature
Alarm Actuation Level
Ch2
P681
Motor Overtemperature
Alarm Actuation Level
Ch3
P685
Motor Overtemperature
Alarm Actuation Level
Ch4
P689
Motor Overtemperature
Alarm Actuation Level
Ch5
0 to 250
[ 124 ]
ºC
NOTE!
The value programmed for the motor overtemperature alarm
actuation must be bigger that the value programmed for
reset of the alarm.
It programs the level of the motor overtemperature alarm actu-
ation. Normally a value 20% below of the insulation class of the
motor is used.
If the motor temperature exceed the programmed level and
the corresponding channel is programmed for alarm, the motor
continues running and will be indicated alarm message in the
display of the HMI.