![WEG SSW06 User Manual Download Page 17](http://html.mh-extra.com/html/weg/ssw06/ssw06_user-manual_950614017.webp)
17
SSW-06 - QUICK PARAMETER REFERENCE
MOTOR PARAMETERS
P400 to P499
P400
(1)
Nominal Motor Voltage
0 to 999
380
V
118
P401
(1)
Nominal Motor Current
0 to 2424
20
A
118
P402
(1)
Nominal Motor Speed
400 to 3600
1780
rpm
118
P404
(1)
Nominal Motor Power
0.1 to 2650
75
kW
118
P405
(1)
Motor Power Factor
0 to 1.00
0.89
-
118
P406
(1)
Service Factor
0 to 1.50
1.00
-
119
SPECIAL FUNCTION PARAMETERS P500 to P599
Braking
P500
(1)
Braking Methods
0=Inactive
0=Inactive
-
119
1=Reverse Braking
2=Optimal Braking
3=DC-Braking
P501
Braking Time
1 to 299
10
s
122
P502
Braking Voltage Level
30 to 70
30
%
122
P503
Braking End Detection
0=Inactive
0=Inactive
-
122
1=Automatic
JOG
P510
(1)
Jog
0=Inactive
0=Inactive
-
123
1=Active
P511
Jog Level
10 to 100
30
%
123
Kick Start
P520
(1)
Kick Start Torque Pulse
0=Inactive
0=Inactive
-
124
(according to P202)
1=Active
P521
Kick Start Pulse Time
0.1 to 2
0.1
s
124
P522
Kick Start Voltage Pulse Level
70 to 90
70
%
124
(% Un of the Motor)
P523
Kick Start Current Pulse Level
300 to 700
500
%
124
(% In of the Motor)
PROTECTION PARAMETERS
P600 to P699
Voltage Protection
P600
(1)
Immediate Undervoltage
0 to 30
20
%
125
(% Un of the Motor)
P601
(1)
Immediate Undervoltage Time
0=Inactive
1
s
125
1 to 99
P602
(1)
Immediate Overvoltage
0 to 30
15
%
125
(% Un of the Motor)
P603
(1)
Immediate Overvoltage Time
0=Inactive
1
s
125
1 to 99
P604
(1)
Voltage Imbalance between Phases
0 to 30
15
%
125
(% Un of the Motor)
P605
(1)
Voltage Imbalance between
0=Inactive
1
s
125
Phases Time
1 to 99
Current Protection
P610
(1)
Immediate Undercurrent
0 to 99
20
%
126
(% In of the Motor)
P611
(1)
Immediate Undercurrent Time
0=Inactive
0=Inactive
s
126
1 to 99
P612
(1)
Immediate Overcurrent
0 to 99
20
%
126
(% In of the Motor)
Parameter
Description
Adjustable Range
Factory
Unit
User´s
Page
Setting Setting
Summary of Contents for SSW06
Page 2: ......