CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
135
Range
[Factory Setting]
Parameter
Unit
Description / Notes
NOTE!
As there are several Thermal Protection Classes, you must
program that Thermal Protection Class that best meets your
application and protects the motor during its allowed duty.
NOTE!
The SSW-06 Soft-Starter thermal class times are an evolution of
the previous WEG Soft-Starters, therefore the times are different
to those of the SSW-03 and SSW-04. The class to be adopted
must be in accordance with the SSW-06 graphs.
NOTE!
When using a motor with a PTC thermal sensor or thermostat
connected to the SSW-06 Soft-Starter, there is no need to enable
the Thermal Classes, therefore set P640=0.
Sets the time for the auto-reset of the thermal image of the motor.
This function can be used for applications that require several starts
per hour or those with short intervals of time between starting and
stopping the motor.
The motor cooling curves are based on many years of experience
of WEG developing motors. They adopt the Standard IP55 Three
Phase Motors with temperature elevation of 60K as a standard.
They also consider if the motor is cool when switched on or not.
The thermal image cool time depends on the power of the motor, in
other words, for each power rating there is a different cooling time.
The thermal image can also be reset if parameter P640=0 is pro-
grammed, returning to the desired Thermal Class afterwards.
P641
(1)
0 to 600
Auto-Reset of the
[ 0=Inactive ]
Thermal Memory
1s
Motor
On
Off
Actuation
Level
Motor
On
Off
Actuation
Level
Auto-reset
time
with reset
E05
t
t
t
whithout
reset
E05
t
Figure 6.30
- Auto-reset of the thermal memory
NOTE!
Please consider, that when using this function, the useful life
time of the motor winding can be reduced.