CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
110
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P204
Action
0, 1, 2,
Not used:
6, 9, 12
No action
3
Resets the parameters from P043 to P050
4
Resets the parameters from P053 to P058
5
Loads Factory Default:
Loads current Soft-Starter parameters
with factory settings
7
Loads User 1:
Loads current Soft-Starter
parameters
with the values stored in Memory 1.
8
Loads User 2:
Loads current Soft-Starter
parameters
with the values stored in Memory 2.
10
Save User 1:
Transfers the current parameter
contents of the Soft-Starter to memory 1
11
Save User 2:
Transfers the current parameter
contents of the Soft-Starter to memory 2
13
Erases the SoftPLC applicative
14
Resets the parameters from P952 to P969
15, 16
Use reserved to the factory
NOTE!
Parameter loading/saving will be executed only after parameter
setting and after the key has been pressed .
This Parameter selects which parameter listed in table 6.23 will be
displayed after the Soft-Starter has been powered-up.
P205
0 to 9
Display Default
[ 2 ]
Selection -
Table 6.22
- Action of loading/saving parameters
Table 6.23
- Options display default
In the event of a fault trip E03, E04, E05, E06, E16, E32, E65, E66,
E70, E74, E78, E79, E80 or E81, the Soft-Starter SSW-06 can initiate
an automatic reset after the time given by P206 has elapsed.
If P206
≤
2 Auto-Reset does not occur.
If after Auto-Reset the same fault is repeated three times consecu-
P206
0 to 600
Auto-Reset Time
[ 0=Inactive ]
1s
P205
Status
0
P001 (Soft-Starter current % In of the Soft-Starter)
1
P002 (Motor current % In of the Motor)
2
P003 (Motor current (A))
3
P004 (Supply Line Voltage (V))
4
P005 (Supply Line Frequency (Hz)
5
P006 (Soft-Starter Status)
6
P007 (Output Voltage (V))
7
P008 (Power Factor)
8
P009 (Motor Torque % Tn of the Motor)
9
P010 (Output Power)