DETAILED PARAMETER DESCRIPTION
This Chapter describes in detail all Soft-Starter SSW-06 parameters. In order
to simplify the explanation, the parameters have been grouped by characte-
ristics and functions:
Symbols and definitions used in the text below:
(1)
Indicates that the parameter can only be changed when the Soft-Starter
SSW-06 is disabled (motor stopped).
(2)
Parameters not changed when programmed to Factory Default (P204=5).
6.1 ACCESS AND READ ONLY PARAMETERS - P000 to P099
This parameter opens the access to change the parameter values.
When values are set according to Factory Default [P200 = 1 (Pas-
sword is active)] set P000 = 5 to change parameter values, and the
Password value is equal to 5.
By programming P000 with the password that releases access to
change parameter contents, plus 1 (Pa 1), you will obtain
access only to the parameters with contents different from the factory
setting.
To change the password to any other value (password 1), proceed
as follows:
(1)
Set P000=5 (current password) and P200= 0 (password inactive).
(2)
Press the key
.
(3)
Change P200 to 1 (password active).
(4)
Press the key
again: display shows P000.
(5)
Press the key
again: display shows 5 (last password).
(6)
Use the keys
and
to change to the desired password
value (password 1).
(7)
Press the key
: display shows P000. From this moment on,
the new password becomes active. Thus, to change parameter
content P000 must be set to the new password. (Password 1).
P000
0 to 999
Parameter Access
[0]
Password Value
-
Setting
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Read Only Parameters
Variables that can only be viewed on the display but
not changed by the user.
Regulation Parameters
Programmable values used by the Soft-Starter
SSW-06 functions.
Configuration Parameters
These Parameters define the Soft-Starter
SSW-06 characteristics, the functions to be executed,
as well as the input/output functions of the control board.
Motor Parameters
Motor data that are indicated on the motor nameplate.
Special Function Parameters
Here are the parameters related to special functions.
Protection Parameters
Here are the parameters related to actuation levels
and actuation time of the motor protection.