![WEG SSW06 User Manual Download Page 18](http://html.mh-extra.com/html/weg/ssw06/ssw06_user-manual_950614018.webp)
SSW-06 - QUICK PARAMETER REFERENCE
18
Parameter
Description
Adjustable Range
Factory
Unit
User´s
Page
Setting Setting
P613
(1)
Immediate Overcurrent Time
0=Inactive
0=Inactive
s
126
1 to 99
P614
(1)
Current Imbalance between Phases
0 to 30
15
%
126
(% In of the Motor)
P615
(1)
Current Imbalance between 0=Inactive
1 s
126
Phases Time
1 to 99
P616
(1)
Undercurrent before
0=Inactive
1=Active -
127
By-pass Closing 1=Active
P617
(1)
Locked Rotor at the
0=Inactive
1=Active -
127
Start End
1=Active
P618
(1)
Ground Fault
10 to 30
20
%
127
P619
(1)
Ground Fault Time
0 to 10.0
0=Inactive
s
127
Phase Sequence
P620
(1)
RST Phase Sequence
0=Inactive
0=Inactive
-
127
1=Active
By-pass Contactor Closed Detection
P621
(1)
By-pass Contactor Closed 0=Inactive
1=Active
127
1=Active
By-pass Contactor Closed Detection
P622
(1)
Short Circuit in the SSW Power 0=Inactive
0=Inactive
127
1=Active
Interval between Starts
P630
Interval of Time after Stop
2 to 999
2
s
127
Short Circuit Detection in the Power of the SSW
P640
(1)
Motor Protection Thermal Class
0=Inactive 5=25
6=30
-
129
1=5 6=30
2=10 7=35
3=15 8=40
4=20 9=45
P641
(1)
Auto-Reset of the Thermal Memory
0=Inactive
0=Inactive
s
132
1 to 600
P642
Motor Thermal Protection Alarm
0 to 250
230
%
133
P643
Motor Thermal Protection Alarm Reset 0 to 250
210
%
133
Torque Protections
P650
(1)
Immediate Undertorque
0 to 99
30
%
133
(% Tn of the Motor)
P651
(1)
Immediate Undertorque Time
0 to 99
0=Inactive
s
133
P652
(1)
Immediate Overtorque
0 to 99
30
%
133
(% Tn of the Motor)
P653
(1)
Immediate Overtorque Time
0 to 99
0=Inactive
s
133
Power Protections
P660
(1)
Immediate Underpower
0 to 99
30
%
134
(% kWn of the Motor)
P661
(1)
Immediate Underpower Time
0 to 99
0=Inactive
s
134
P662
(1)
Immediate Overpower
0 to 99
30
%
134
(% kWn of the Motor)
P663
(1)
Immediate Overpower Time
0 to 99
0=Inactive
s
134
Motor Thermal Protection (Optional PT100)
P670
PT100 Inputs Card Enable
0=No
0=No -
134
1=Yes
P671
Motor Overtemperature Ch 1
0=
Inactive
0=
Inactive
-
135
1=Error E33
Summary of Contents for SSW06