![WEG SSW06 User Manual Download Page 34](http://html.mh-extra.com/html/weg/ssw06/ssw06_user-manual_950614034.webp)
CHAPTER 3 - INSTALLATION AND CONNECTION
34
Use the minimum recommended panel dimensions and its cooling
requirements:
NOTE!
The fans recommended in table 3.3 are base on:
- a working cycle of 10 starts per hour with 3 x In of the SSW-06 for
30s at an ambient temperature of 55°C (131°F) for the models from
10A to 820A;
- a working cycle of 5 starts per hour with 30s at an ambient tempe-
rature of 40°C (104°F) for the models from 950A to 1400A.
Table 3.3
- Panel Dimensions and Cooling Requirements
Model
Panel Dimensions
Cooling
m
3
/min (CFM)
Width W
mm (in)
Heigth H
mm (in)
Depth D
mm (in)
220-575V
575-690V
SSW06.0010
-
600
(23.62)
800
(31.49)
300
(11.81)
-
SSW06.0016
-
SSW06.0023
-
SSW06.0030
-
SSW06.0045
SSW06.0045
600
(23.62)
1,000
(39.37)
400
(15.75)
-
SSW06.0060
SSW06.0060
SSW06.0085
SSW06.0085
SSW06.0130
-
SSW06.0170
SSW06.0130
600
(23.62)
1,200
(47.24)
400
(15.75)
-
SSW06.0205
SSW06.0170
-
SSW06.0205
600
(23.62)
1,600
(63.00)
600
(23.62)
-
SSW06.0255
SSW06.0255
SSW06.0312
SSW06.0312
600
(23.62)
2,000
(78.74)
600
(23.62)
-
SSW06.0365
SSW06.0365
SSW06.0412
SSW06.0412
600
(23.62)
2,000
(78.74)
600
(23.62)
-
SSW06.0480
SSW06.0480
SSW06.0604
SSW06.0604
SSW06.0670
SSW06.0670
800
(31.5)
2,000
(78.74)
600
(23.62)
-
SSW06.0820
SSW06.0820
SSW06.0950
SSW06.0950
800
(31.5)
2,000
(78.74)
600
(23.62)
49.8
(1,757.30)
SSW06.1100
SSW06.1100
800
(31.5)
2,000
(78.74)
600
(23.62)
49.8 (1,757.30)
SSW06.1400
SSW06.1400
75.0 (2,648.44)
Summary of Contents for SSW06