CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
127
Range
[Factory Setting]
Parameter
Unit
Description / Notes
The Soft-Starter SSW-06 allows for the use of a torque pulse during
the starting process for loads that have high resistance during the
starting process.
Enabled through P520=1. The duration of this pulse may be adjusted
at P521.
This pulse will be applied according to the type of control selected
at P202:
- Voltage ramp: the voltage level may be set at P522.
- Current limit: the current level may be set at P523.
- Current ramp: with adjustable current level at P523.
NOTES!
1) Use this function only for specific applications, when required.
2) This function is not required for Torque Control.
P520
(1)
0 to 1
Kick Start
[ 0=Inactive ]
Torque Pulse
-
P521
0.1 to 2
Kick Start
[ 0.1 ]
Pulse Time
0.1s
P522
70 to 90
Kick Start
[ 70 ]
Voltage Pulse Level 1 %Un of the motor
P523
300 to 700
Kick Start
[ 500 ]
Current Pulse Level 1 %In of the motor
Figure 6.22
- Actuation levels of the starting torque pulse
Start
I(A)
I Limit
t(s)
P102
Disable
Enable
Current Ramp
0
P110
P523
P521
Nominal Current
Maximum Time
P112
P111
Start
I(A)
I Limit
t(s)
P102
Disable
Enable
Current Limit
0
P110
P523
P521
I Nominal
Start
U(V)
100%Un
t(s)
P102
Disable
Enable Voltage Ramp
0
P101
P522
P521