![WEG SSW06 User Manual Download Page 48](http://html.mh-extra.com/html/weg/ssw06/ssw06_user-manual_950614048.webp)
CHAPTER 3 - INSTALLATION AND CONNECTION
48
Table 3.8 presents the short circuit capacity, Standard Fault, of the
power supply (symmetric Arms) at which the SSW-06 can be installed,
provided that protected by means of regular fuses or circuit breakers,
used in the UL tests.
Model
Nominal
Rating
Short Circuit
Rating
≤ 600V
Circuit Breaker
(CB) - UL489
any MCCB
Ultra-fast
Fuses
SSW-06.0010
10 A
5 kA
< 40 A
Ferraz 40 A NTD
SSW-06.0016
16 A
5 kA
< 40 A
Ferraz 60 A NTD
SSW-06.0023
23 A
5 kA
< 40 A
Ferraz 8 0 A NTD
SSW-06.0030
30 A
5 kA
< 40 A
Ferraz 80 A NTD
SSW-06.0045
45 A
5 kA
< 150 A
Ferraz 125 A NTD
SSW-06.0060
60 A
5 kA
< 150 A
Ferraz 125 A NTD
SSW-06.0085
85 A
10 kA
< 150 A
Bussmann 200 A
SSW-06.0130
130 A
10 kA
< 225 A
Bussmann 250 A
SSW-06.0170
170 A
10 kA
< 250 A
Bussmann 450 A
SSW-06.0205
205 A
10 kA
< 250 A
Bussmann 500 A
SSW-06.0255
255 A
18 kA
< 400 A
Bussmann 500 A
SSW-06.0312
312 A
18 kA
< 400 A
Bussmann 500 A
SSW-06.0365
365 A
18 kA
< 600 A
Bussmann 550 A
SSW-06.0412
412 A
18 kA
< 600 A
Bussmann 700 A
SSW-06.0480
480 A
30 kA
< 600 A
Bussmann 900 A
SSW-06.0604
604 A
42 kA
< 800 A
Bussmann 900 A
SSW-06.0670
670 A
42 kA
< 1200 A
Bussmann 900 A
SSW-06.0820
820 A
42 kA
< 1200 A
Bussmann 1400 A
SSW-06.0950
950 A
42 kA
< 1200 A
Bussmann 1600 A
SSW-06.1100
1100 A
85 kA ≤ 480 V
< 1600 A
Bussmann 1600 A
SSW-06.1400
1400 A
85 kA ≤ 480 V
< 2000 A
Bussmann 2000 A
Table 3.8
- Short circuit capacity standard connection - UL Standard Fault
The fuses in table 3.8 used in the SSW-06 UL tests are of the ultra-
fast (aR) type, which also reduce the risk of SCRs being burned by
over current transients.
Table 3.9, presents the short circuit capacity, High Fault, of the power
supply (symmetric Arms) at which the SSW-06 can be installed within
a closed panel, standard connection, provided that protected by means
of circuit breakers, used in the UL tests
.
3.2.4.1 Short Circuit Capacity,
Fuses, Circuit Breaker - UL
Summary of Contents for SSW06