CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
123
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Figure 6.19
- Reverse Braking
Start
U(V)
100%Un
Enable
Disable
Start
P502
t(s)
P501
FWD/REV-K2 Closed
FWD/REV-K1 Closed
1s
0
NOTES!
1. The contactors must be the same model and withstand
the motor starting current. For security, use an auxiliary
contact to avoid contactors closing at the same time.
2. Use the digital input set to “General Enable” to stop the
motor without braking.
3. For security a digital input should be programmed which
is wired from a zero speed sensor, and set to “Braking
Off”, so that starting the motor in the wrong direction will
be avoided.
4. The Soft-Starter SSW-06 protects the motor while the
Reverse Braking AC level is applied.
5. See parameters: P266, P267, P268, P277, P278, P500,
P501, P502, and P503 and see the recommended setup
at items 3.3 and 3.3.9.
“Optimal Braking”
This is an efficient method to stop loads.
The direct current is only applied when it produces a braking effect.
No contactor needed.
It is compatible with the Soft-Starter SSW-06 inside delta motor
connection, except for two and eight pole motors.
Figure 6.20
- Optimal Braking
Start
U(V)
100%Un
Enable
Disable
P501
t(s)
P502
1s
0