CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
91
Range
[Factory Setting]
Parameter
Unit
Description / Notes
RL1...RL3 Status
P013=101
Indicates on the keypad LCD display the status of the 3 relay outputs
of the control board. Number 1 stands for Active and 0 for Inactive,
in the following order:
RL1, RL2, RL3.
The keypad LED display shows the decimal value that corresponds
to the status of the 3 digital outputs, where the status of each output
is considered one bit in the specified sequence:
Inactive=0
Active=1
RL1 status is the most significant bit.
The 5 least significant bits are always "0".
Example:
RL1=Active; RL2=Inactive; RL3=Active
This is equivalent to the binary sequence:
10100000
Which corresponds to the decimal number 160.
The least significant bits are not displayed.
The Keypad displays will be:
P013
LCD=1,0
RL1 to RL3 Status
LED=0 to 255
[ - ]
-
Indicate the code of the last previous Faults.
Fault Sequence:
Exy
→
P014
→
P015
→
P016
→
P017
→
P018
→
P019
P014
0 to 99
Last Fault
[ - ]
-
P015
0 to 99
Second Previous
[ - ]
Fault -
P016
0 to 99
Third Previous
[ - ]
Fault -
P017
0 to 99
Fourth Previous
[ - ]
Fault -
P018
0 to 99
Fifth Previous
[ - ]
Fault -
P019
0 to 99
Sixth Previous
[ - ]
Fault -