CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
125
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P501 sets the maximum time that the braking voltage is applied.
ATTENTION!
1. This is the main protection of all braking methods. Set it
according to the application, so that the Soft-Starter SSW-
06 and the motor can withstand the settings.
2. The parameters: P001, P002, P003, P008, P009, P010
and P011 are set to zero during Optimal Braking and DC-
-Braking.
3. The current protections do not work with a DC current
because the current transformers saturate with DC current.
4. The Soft-Starter SSW-06 does not protect the motor while
it is performing braking, if no motor PTC sensor is used.
P501
Braking Time
1 to 299
[ 10 ]
1s
P502 sets the braking voltage level. It is based on the AC line voltage
converted to DC voltage.
This parameter also sets the level of the AC Reverse Braking.
ATTENTION!
1. Be careful with this voltage level. Set it according to the
application so that the Soft-Starter SSW-06 and the motor
can withstand the settings.
2. Start with low voltage levels and increase them according
to the need.
3. The current protections do not work with a DC current
because the current transformers saturate with DC current.
4. The Soft-Starter SSW-06 does not protect the motor while
it is performing the braking, if no motor PTC sensor is used.
5. To measure this current during braking you need a special
current meter with hall effect transformers.
P502
Braking Voltage Level
30 to 70
[ 30 ]
%
P503
Braking End Detection
0 to 1
[ 0=Inactive ]
-
Table 6.39
- Braking end detection
This parameter sets the automatic detection of the motor standstill.
NOTES!
1. This function does not work with two and eight pole motors.
2. This function does not work with inside delta motor con-
nections.
3. The motor standstill detection can vary with the motor
temperature.
4. Always use the braking time (P501) as the main protection.
P503 Description
0
Inactive
1
Automatic