![WEG SSW06 User Manual Download Page 89](http://html.mh-extra.com/html/weg/ssw06/ssw06_user-manual_950614089.webp)
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
89
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P006
0 to 12
Soft-Starter SSW-06
[ - ]
Status
1
Indicates the actual Soft-Starter SSW-06 status:
Table 6.1
- Soft-Starter status
Indicates motor power factor.
Accuracy: ± 5%.
NOTE!
The motor power factor will only be indicated when the current
is greater than 20% of the nominal current of the SSW-06.
0 (Zero) will be indicated if the current is below 20% of the
SSW-06 nominal current.
P008
0 to 1.00
Power Factor
[ - ]
-
Indicates the average True rms voltage of the three output phases
of the Soft-Starter SSW-06 in Volts (V).
Accuracy: ± 2V.
NOTE!
The voltage will only be indicated when it reaches a value greater
than 15V. Below this value, only 0 (zero) will be indicated.
P007
0 to 999
Soft-Starter SSW-06
[ - ]
Output Voltage
1V
P009
0 to 999.9
Motor Torque
[ - ]
0,1%
Indicates the motor torque in percent of the nominal motor torque
(% Tn of the Motor).
The Soft-Starter SSW-06 is fitted with a software for estimating
the motor torque by using the same principles contained in WEG
Frequency Inverters.
This high technology software enables indicating the motor torque
very close to the effective present torque.
Accuracy of ± 10% Tn of the Motor.
ATTENTION!
Information related to the nominal torque of the motor and
maximum starting torque of the motor can be found in the
manufacturer’s catalogue.
NOTE!
For the correct torque to be indicated, in P009, all the para-
meters related to the motor, P400 to P406, must be correctly
programmed according to the data informed on the motor
nameplate.
P006
Description of the Soft-Starter status
0
Ready to start the motor
1
Performing the initial test of the line and of the motor
2
With a fault
3
During acceleration ramp
4
At full voltage
5
With the By-pass contactor activated
6
Reserved
7
During deceleration ramp
8
Performing braking
9
Performing reversion of the speed direction
10
During Jog
11
During the P630 time delay
12
With the General Enable deactivated
Summary of Contents for SSW06
Page 2: ......