SSW-06 - QUICK PARAMETER REFERENCE
Parameter
Description
Adjustable Range
Factory
Unit
User´s
Page
Setting Setting
2=Alarm A33
3=E33 and A33
P672
Motor Overtemperature
Error
0 to 250
139
ºC
136
Actuation
Level Ch 1
P673
Motor Overtemperature Alarm
0 to 250
124
ºC
136
Actuation Level Ch 1
P674
Motor Overtemperature Alarm
0 to 250
108
ºC
137
Reset Level Ch 1
P675
Motor Overtemperature Ch 2
0=
Inactive
0=
Inactive
-
137
1=Error E34
2=Alarm A34
3=E34 and A34
P676
Motor Overtemperature Error
0 to 250
139
ºC
136
Actuation
Level Ch 2
P677
Motor Overtemperature Alarm
0 to 250
124
ºC
136
Actuation Level Ch 2
P678
Motor Overtemperature Alarm
0 to 250
108
ºC
137
Reset Level Ch 2
P679
Motor Overtemperature Ch 3
0=
Inactive
0=
Inactive
-
137
1=Error E35
2=Alarm A35
3=E35 and A35
P680
Motor Overtemperature Error
0 to 250
139
ºC
136
Actuation
Level Ch 3
P681
Motor Overtemperature Alarm
0 to 250
124
ºC
136
Actuation Level Ch 3
P682
Motor Overtemperature Alarm
0 to 250
108
ºC
137
Reset Level Ch 3
P683
Motor Overtemperature Ch 4
0=
Inactive
0=
Inactive
-
137
1=Error E36
2=Alarm A36
3=E36 and A36
P684
Motor Overtemperature Error
0 to 250
139
ºC
136
Actuation
Level Ch 4
P685
Motor Overtemperature Alarm
0 to 250
124
ºC
136
Actuation Level Ch 4
P686
Motor Overtemperature Alarm
0 to 250
108
ºC
137
Reset Level Ch 4
P687
Motor Overtemperature Ch 5
0=
Inactive
0=
Inactive
-
137
1=Error E37
2=Alarm A37
3=E37 and A37
P688
Motor Overtemperature Error
0 to 250
139
ºC
136
Actuation
Level Ch 5
P689
Motor Overtemperature Alarm
0 to 250
124
ºC
136
Actuation Level Ch 5
P690
Motor Overtemperature Alarm
0 to 250
108
ºC
137
Reset Level Ch 5
P691
PT100 Sensors Fault (Ch1 to Ch5)
0=
Inactive
0=
Inactive
-
137
1=E43 to E52
2=A43 to A52
Summary of Contents for SSW06