CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
102
Range
[Factory Setting]
Parameter
Unit
Description / Notes
NOTE!
Choose the type of torque control, easier to program and set,
according to the knowledge about the characteristics of the load.
P121
10 to 400
Initial Starting
[ 30 ]
Torque
1% Tn of the Motor
Enables programming an initial torque limit or a constant during the
start, according to the torque type selected at P120.
For more details about programming and application, refer to Torque
Control at P202.
P122
10 to 400
End Starting
[ 110 ]
Torque
1% Tn of the Motor
It enables programming an end torque limit for the start, when a
linear or quadratic torque has been selected at P120.
For more details about programming and application, refer to Torque
Control at P202.
P123
10 to 400
Minimum Starting
[ 27 ]
Torque
1% Tn of the Motor
It enables programming an intermediate torque limit during the start,
when a quadratic torque has been selected at P120.
For more details about programming and application, refer to Torque
Control at P202.
P124
1 to 99
Time for the Minimum
[ 20 ]
Start Torque
1% of P102
It enables programming the time for the intermediate torque limit
during the start, as a percentage of the maximum time programmed
at P102, when a quadratic torque has been set at P120.
For more details about programming and application, refer to Torque
Control at P202.
Table 6.8
- Function of P121 according to P120
Table 6.9
- Function of P122 according to P120
Table 6.10
- Function of P123 according to P120
Table 6.11
- Function of P124 according to P120
P120
Action
1 (Constant)
P121 limits the maximum torque during the start
2 (Linear)
P121 limits the initial torque during the start
3 (Quadratic) P121 limits the initial torque during the start
P120
Action
1 (Constant)
P122 not used
2 (Linear)
P122 limits the end torque during the start
3 (Quadratic) P122 limits the end torque during the start
P120
Action
1 (Constant)
P123 not used
2 (Linear)
P123 not used
3 (Quadratic) P123 limits the intermediate torque during the start
P120
Action
1 (Constant)
P124 not used
2 (Linear)
P124 not used
3 (Quadratic) P124 time for the intermediate torque limit during the start