CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
124
Range
[Factory Setting]
Parameter
Unit
Description / Notes
NOTES!
1. Use a digital input set to "General Enable" to stop the motor
without braking.
2. Use one digital input set to "Braking Off", for extra safety,
for monitoring the real motor standstill and disables the
braking immediately.
3. For high inertia loads it is recommended to use a PTC
motor input.
4. It is not recommended to use Optimal Braking with two and
eight pole motors.
5. See parameters: P266, P267, P268, P500, P501, P502,
P503 and see the recommended set-up at items 3.3 and
3.3.10.
“DC-Braking”
This is an old and efficient method to stop very high inertia loads.
The direct current is applied all the time until the motor stops.
One contactor is needed to short-circuit the output lines U and V.
The method differs from SSW-03 and SSW-04.
The necessary current to stop the motor is very high and continuously
applied.
It is not compatible with the Soft-Starter SSW-06 inside delta motor
connection.
Figure 6.21
- DC-Braking
NOTES!
1. Use a digital input set to "General Enable" to stop the motor
without braking.
2. Use one digital input set to "Braking Off", for extra safety,
for monitoring the real motor standstill and disabling the
braking immediately.
3. It is recommended to use a PTC motor input.
4. See parameters: P266, P267, P268, P277, P278, P279,
P500, P501, P502, P503 and see the recommended set-up
at items 3.3 and 3.3.11.
Start
U(V)
100%Un
Enable
Disable
P502
t(s)
P501
DC-Brake RLX
Closed
1s
0
Rotation direction K1 closed