Faults and Alarms
P0834 - DIM1 and DIM2 Status
Adjustable
Range:
Bit 0 = DIM1
Bit 1 = DIM2
Factory
Setting:
Properties:
CFW-11M and RO
Access groups
via HMI:
01 PARAMETER GROUPS
or
09 READ ONLY PARAMETERS
40 Digital Inputs
Description:
Through this parameter it is possible to visualize the status of the 2 digital inputs of the Modular Drive interface
board.
The indication is done by means of the numbers 0 and 1, representing respectively the states No Fault/Alarm or
With Fault/Alarm at the inputs.
The state of each input is considered as one digit in the sequence where DIM1 represents the least significant digit.
Refer to the CFW-11M user's manual to obtain more information.
15.4 MOTOR OVERTEMPERATURE PROTECTION USING THE IOE-01, IOE-02 OR IOE-03
MODULE
For each type of temperature sensor, PTC, PT100 or KTY84, there is an optional module associated, IOE-01,
IOE-02 or IOE-03, respectively.
P0374 - Sensor 1 Temperature Fault/Alarm Configuration
P0377 - Sensor 2 Temperature Fault/Alarm Configuration
P0380 - Sensor 3 Temperature Fault/Alarm Configuration
P0383 - Sensor 4 Temperature Fault/Alarm Configuration
P0386 - Sensor 5 Temperature Fault/Alarm Configuration
Adjustable
Range:
0 = Inactive
1 = Temperature Fault/Temperature Alarm/Cable Alarm
2 = Temperature Fault/Cable Alarm
3 = Temperature Alarm/Cable Alarm
4 = Temperature Fault/Temperature Alarm
5 = Temperature Fault
6 = Temperature Alarm
7 = Cable Alarm
Factory
Setting:
1
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
45 Protections
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...