11-37
11
Vector Control
Seq.
Action/Result
Display Indication
10
- If necessary, change
the content of P0296
according to the used line
voltage. Therefore press
"
Select
". This change will
affect P0151, P0153,
P0185, P0190, P0321,
P0322, P0323 and
P0400.
Config LOC
0rpm
Reset
13:48 Select
Type of Control
P0202: Sensorless
Line Rated Voltage
P0296: 440 - 460 V
11
- If necessary, change
the content of P0298
according to the inverter
application. Therefore
press "
Select
". This
change may affect P0156,
P0157, P0158, P0169,
P0170, P0401 and
P0404. The actuation
time and level of the
IGBTs overload protection
will also be affected.
Config LOC
0rpm
Reset
13:48
Select
Line Rated Voltage
P0296: 440 - 460 V
Application
P0298: Normal Duty
12
- If necessary adjust
the content of P0398
according to the motor
service factor. Therefore
press "
Select
". This change
will affect the current
value and the time for the
actuation of the motor
overload function.
Config LOC
0rpm
Reset
13:48 Select
Application
P0298: Normal Duty
Motor Service Factor
P0398: 1.15
13
- If necessary, change
the content of P0400
according to the rated
motor voltage. Therefore
press "
Select
". This change
will affect P0190.
Config LOC
0rpm
Reset
13:48 Select
Motor Service Factor
P0398: 1.15
Motor Rated Voltage
P0400: 440V
14
- If necessary, change
the content of P0401
according to the rated
motor current. Therefore
press "
Select
". This change
will affect P0156, P0157
and P0158.
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Voltage
P0400: 440V
Motor Rated Current
P0401: 13.5 A
Seq.
Action/Result
Display Indication
15
- If necessary, change
the content of P0402
according to the rated
motor speed. Therefore
press "
Select
". This change
may affect P0122 to
P0131, P0133, P0134,
P0182, P0208, P0288
and P0289.
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Current
P0401: 13.5A
Motor Rated Speed
P0402= 1750rpm
16
- If necessary, change
the content of P0403
according to the rated
motor frequency. Therefore
press "
Select
".
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Speed
P0402: 1750 rpm
Motor Rated Frequency
P0403: 60Hz
17
- If necessary, change
the content of P0404
according to the rated
motor power. Therefore
press "
Select
".
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Frequency
P0403: 60Hz
Motor Rated Power
P0404: 7.5hp
18
- This parameter will only be
visible if the encoder board
ENC1, ENC2 or PLC11
module is connected to the
inverter.
- If there is an encoder
connected to the motor,
change P0405 according
to its number of pulses per
revolution. Therefore press
"
Select
".
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Power
P0404: 7.5hp
Encoder Pulses Number
P0405: 1024 ppr
19
- If necessary, change
the content of P0406
according to the type
of motor ventilation.
Therefore press "
Select
".
This change will affect
P0156, P0157, P0158,
P0399 and P0407.
Config LOC
0rpm
Reset
13:48 Select
Encoder Pulses Number
P0405: 1024 ppr
Motor Ventilation
P0406: Self-Vent.
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...