Functions Common to All the Control Modes
P0122 – JOG + Speed Reference
P0123 – JOG - Speed Reference
Adjustable
Range:
0 to 18000 rpm
Factory
Setting:
150 rpm
(125 rpm)
Properties:
PM and Vector
Access groups
via HMI:
01 PARAMETER GROUPS
21 Speed References
Description:
The JOG+ or JOG- commands are always carried out via digital inputs.
One DIx input must be programmed for JOG+ and another for JOG- as presented in the
Table 12.2 -
Selection of the JOG+ and JOG- commands via digital inputs
Digital Input
Function
JOG+
JOG -
DI1
P0263 = 16
P0263 = 17
DI2
P0264 = 16
P0264 = 17
DI3
P0265 = 16
P0265 = 17
DI4
P0266 = 16
P0266 = 17
DI5
P0267 = 16
P0267 = 17
DI6
P0268 = 16
P0268 = 17
DI7
P0269 = 16
P0269 = 17
DI8
P0270 = 16
P0270 = 17
During the JOG+ or JOG- commands the values of P0122 and P0123 are, respectively, added or subtracted from
the speed reference to generate the total reference (refer to the
For the JOG option refer to the previous parameter description.
12.3 SPEED LIMITS [22]
The parameters of this group have the purpose of acting as motor speed limits.
P0132 – Maximum Overspeed Level
Adjustable
Range:
0 to 100 %
Factory
Setting:
10 %
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
22 Speed Limits
Description:
This parameter sets the highest speed allowed for the motor to operate, and must be adjusted as a percentage of
the maximum speed limit (P0134).
When the actual speed exceeds the value of P0134 + P0132 longer than 20 ms, the CFW-11 will disable the PWM
pulses and indicate the fault (F150).
In order to disable this function, set P0132 = 100 %.
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...