15-13
15
Faults and Alarms
Description:
The CFW-11 is equipped with two fans: an internal fan and a heatsink fan, and the activation of both will be
controlled via software by means of the inverter programming.
The options available for the setting of this parameter are the following:
Table 15.5 -
Options of the parameter P0352
P0352
Action
0 = HS-OFF, Int-OFF
Heatsink fan is always OFF
Internal fan is always OFF
1 = HS-ON, Int-ON
Heatsink fan is always ON
Internal fan is always ON
2 = HS-CT, Int-CT
Heatsink fan is controlled via software
Internal fan is controlled via software
3 = HS-CT, Int-OFF
Heatsink fan is controlled via software
Internal fan is always OFF
4 = HS-CT, Int-ON
Heatsink fan is controlled via software
Internal fan is always ON
5 = HS-ON, Int-OFF
Heatsink fan is always ON
Internal fan is always OFF
6 = HS-ON, Int-CT
Heatsink fan is always ON
Internal fan is controlled via software
7 = HS-OFF, Int-ON
Heatsink fan is always OFF
Internal fan is always ON
8 = HS-OFF, Int-CT
Heatsink fan is always OFF
Internal fan is controlled via software
9 = HS-CT, int-CT *
Heatsink fan is controlled via software
Internal fan is controlled via software (*)
10 = HS-CT, int-OFF *
Heatsink fan is controlled via software
Internal fan is always OFF (*)
11 = HS-CT, int-ON *
Heatsink fan is controlled via software
Internal fan is always ON (*)
12 = HS-ON, int-CT *
Heatsink fan is always ON
Internal fan is controlled via software (*)
13 = HS-OFF, int-CT *
Heatsink fan is always OFF
Internal fan is controlled via software (*)
(*)
The fans will not turn on for one minute after the power-on or after a fault reset.
A delay of fifteen seconds was introduced to turn on (off) the fan after it has been turned off (on).
P0353 – IGBTs and Internal Air Overtemperature Protection
Adjustable
Range:
0 = IGBTs: fault and alarm, Internal air: fault and alarm
1 = IGBTs: fault and alarm, Internal air: fault
2 = IGBTs: fault, Internal air: fault and alarm
3 = IGBTs: fault, Internal air: fault
4 = IGBTs: fault and alarm, Internal air: fault and alarm (*)
5 = IGBTs: fault and alarm, Internal air: fault (*)
6 = IGBTs: fault, Internal air: fault and alarm (*)
7 = IGBTs: fault, Internal air: fault (*)
Factory
Setting:
0
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
45 Protections
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...