Vector Control
11-20
11
11.8.3 Flux Regulator [92]
The parameters related to the CFW-11 flux regulator are presented next.
P0175 – Flux Regulator Proportional Gain
Adjustable
Range:
0.0 to 31.9
Factory
Setting:
2.0
P0176 – Flux Regulator Integral Gain
Adjustable
Range:
0.000 to 9.999
Factory
Setting:
0.020
Properties:
Vector
Access groups
via HMI:
01 PARAMETER GROUPS
29 Vector Control
92 Flux Regulator
Description:
These parameters are adjusted automatically in function of the parameter P0412. In general, the automatic setting
is sufficient and the readjustment is not necessary.
These gains must only be readjusted manually when the flux current signal (Id*) is unstable (oscillating) and
compromising the system operation.
NOTE!
For gains in P0175>12.0 the flux current (Id*) may become unstable.
Note:
(Id*) is observed at the analog outputs AO3 and/or AO4, by setting P0257 = 22 and/or P0260 = 22.
P0178 – Rated Flux
Adjustable
Range:
0 to 120 %
Factory
Setting:
100 %
Description:
The parameter P0178 is the flux reference.
NOTE!
This parameter must not be changed.
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...