Faults and Alarms
15-14
15
Description:
The overtemperature protection is carried out by means of the measurement of the temperature with the IGBTs and
power board internal air NTCs, being able to generate alarms and faults.
In order to configure the desired protection, set P0353 according to the table below.
Table 15.6 -
Options of the parameter P0353
P0353
Action
0 = HS-F/A, Air-F/A
Enables fault (F051) – IGBT Overtemperature and alarm (A050) – IGBT High Temperature
Enables fault (F153) – Internal Air Overtemperature and alarm (A152) – Internal Air High
Temperature
Enable Alarm of Overtemperature on the Rectifier (A010)
1 = HS-F/A, Air-F
Enables fault (F051) and alarm (A050) for IGBTs overtemperature
Enables only fault (F153) for internal air overtemperature
Enable Alarm of Overtemperature on the Rectifier (A010)
2 = HS-F, Air-F/A
Enables only fault (F051)for IGBT overtemperature
Enables fault (F153) and alarm (A152) for internal air overtemperature
3 = HS-F, Air-F
Enables only fault (F051)for IGBT overtemperature
Enables only fault (F153) for internal air overtemperature
4 = HS-F/A, Air-F/A *
Enables fault (F051) – IGBT Overtemperature and alarm (A050) – IGBT High Temperature
Enables fault (F153) – Internal Air Overtemperature and alarm (A152) – Internal Air High
Temperature
Enable Alarm of Overtemperature on the Rectifier (A010) (*)
5 = HS-F/A, Air-F *
Enables fault (F051) and alarm (A050) for IGBTs overtemperature
Enables only fault (F153) for internal air overtemperature
Enable Alarm of Overtemperature on the Rectifier (A010) (*)
6 = HS-F, Air-F/A *
Enables only fault (F051)for IGBT overtemperature
Enables fault (F153) and alarm (A152) for internal air overtemperature (*)
7 = HS-F, Air-F *
Enables only fault (F051)for IGBT overtemperature
Enables only fault (F153) for internal air overtemperature (*)
(*)
Disable alarm (A155) and fault (F156).
P0354 – Fan Speed Fault Configuration
Adjustable
Range:
0 = Alarm
1 = Fault
Factory
Setting:
1
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
45 Protections
Description:
This parameter allows setting whether a fault or an alarm should take place when the heatsink fan reaches ¼ of the
rated speed. If set to 1, the fault F179 will occur and the inverter will be disabled. If set to 0, the alarm A178 will
occur and the inverter won't be disabled.
Table 15.7 -
Actions for the parameter P0354 options
P0354
Action
0 = Off
The heatsink fan speed fault protection is disabled
1 = Fault
It enables the fault (F179). The inverter will be disabled if the fault occurs
P0355 – Configuration of Fault F185
Adjustable
Range:
0 = Off
1 = On
Factory
Setting:
1
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
45 Protections
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...