PM Vector Control
Seq.
Action/Result
Display Indication
14
- If necessary, change
the content of P0401
according to the rated
motor current. Therefore
press
"Selec."
. This
change will affect P0156,
P0157 and P0158.
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Voltage
P0400: 440V
Motor Rated Current
P0401: 13.5 A
15
- If necessary, change
the content of P0402
according to the rated
motor speed. Therefore
press
"Selec."
. This
change will affect P0122
to P0131, P0133, P0134,
P0208, P0288, P0289
and P0403.
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Current
P0401: 13.5A
Motor Rated Speed
P0402: 1750 rpm
16
- P0403 is automatically
adjusted according to:
P0403 = P0402 x P0431
120
Therefore press
"Selec."
.
Config LOC
0rpm
Reset
13:08 Select
Motor Rated Speed
P0402: 1750 rpm
Motor Rated Frequency
P0403: 60 Hz
17
- If necessary, change
the content of P0404
according to the rated
motor power. Therefore
press
"Selec."
.
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Frequency
P0403: 60 Hz
Motor Rated Power
P0404: 4hp 3kW
18
- This parameter will only
be visible if the encoder
board ENC1 or the PLC11
module is connected to
the inverter.
- If there is an encoder
connected to the motor,
change P0405 according
to its number of pulses per
revolution. Therefore press
"Selec."
.
Config LOC
0rpm
Reset
13:48 Select
Motor Rated Power
P0404: 4hp 3kW
Encoder Pulse Number
P0405: 1024 ppr
Seq.
Action/Result
Display Indication
19
- Set P0409 according to
the motor data sheet.
Therefore, press
"Selec."
.
- If the information is not
available, keep the setting
equal to zero.
Config LOC
0rpm
Reset
13:48 Select
Encoder Pulses Number
P0405: 1024 ppr
Stator Resistence
P0409: 0.000 ohm
20
Adjust P0431 equal to 6
for the standard Wmagnet
motor.
Therefore press
"Selec."
.
This change will affect
P0403.
Config LOC
0rpm
Reset
13:48 Selec.
Resistencia Estator
P0409:
0.000 ohm
Numero de Polos
P0431: 6
21
Adjust P0433 according to
the nameplate data.
Therefore press
"Selec."
.
Config LOC
0rpm
Reset
13:48 Selec.
Numero de Polos
P0431:
6
Indutancia Lq
P0433: 0.00 mH
22
Adjust P0434 according to
the nameplate data.
Therefore press
"Selec."
.
Config LOC
0rpm
Reset
13:48 Selec.
Indutancia Lq
P0433:
0.00 mH
Indutancia Ld
P0434: 0.00 mH
23
Adjust P0435 according to
the nameplate data.
Therefore press
"Selec."
.
Config LOC
0rpm
Reset
13:48 Selec.
Indutancia Ld
P0434:
0.00 mH
Constante Ke
P0435: 100.0
Figure 21.4 -
PM vector mode oriented Start-up
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...