Digital and Analog Inputs and Outputs
Table 13.4 -
Full scale
SCALE OF THE ANALOG OUTPUT INDICATIONS
Variable
Full Scale (*)
Speed Reference
P0134
Total Reference
Real Speed
Encoder Speed
Torque Current Reference
2.0 x I
nomHD
Torque Current
Torque Current > 0
Motor Torque
2.0 x I
nom
Output Current
1.5 x I
nomHD
Active Current
PID Process Variable
P0528
PID Setpoint
Output Power
1.5 x
√3
x P0295 x P0296
Motor Ixt
100 %
SoftPLC
32767
P0696 Value
P0697 Value
P0698 Value
P0699 Value
(*)
When the signal is inverse (10 to 0 V, 20 to 0 mA or 20 to 4 mA) the values
in the table become the beginning of the scale.
P0253 – AO1 Signal Type
P0256 – AO2 Signal Type
Adjustable
Range:
0 = 0 to 10 V/20 mA
1 = 4 to 20 mA
2 = 10 V/20 mA to 0
3 = 20 to 4 mA
Factory
Setting:
0
P0259 – AO3 Signal Type
P0262 – AO4 Signal Type
Adjustable
Range:
0 = 0 to 20 mA
1 = 4 to 20 mA
2 = 20 mA to 0
3 = 20 to 4 mA
4 = 0 to 10 V
5 = 10 to 0 V
6
= -10 to +10 V
Factory
Setting:
4
Properties:
CFG
Access groups
via HMI:
07 I/O CONFIGURATION
or
01 PARAMETER GROUPS
39 Analog Outputs
39 Analog Outputs
Description:
These parameters configure if the analog output signal will be in current or voltage, with direct or inverse reference.
In order to adjust these parameters, it is also necessary to set the "DIP switches" of the control board or of the IOA
Accessory Board, according to the
,
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...