Vector Control
11-12
11
Description:
Set it according to the used motor nameplate data, taking into consideration the motor voltage.
In the Guided Start-up routine the value adjusted in P0401 automatically modifies the parameters related to the
motor overload protection, according to the
.
P0402 – Motor Rated Speed
Adjustable
Range:
0 to 18000 rpm
Factory
Setting:
1750 rpm
(1458 rpm)
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
43 Motor Data
Description:
Set it according to the used motor nameplate data.
For V/f and VVW controls the setting is from 0 to 18000 rpm.
For vector control the setting is from 0 to 7200 rpm.
P0403 – Motor Rated Frequency
Adjustable
Range:
0 to 300 Hz
Factory
Setting:
60 Hz
(50 Hz)
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
43 Motor Data
Description:
Set it according to the used motor nameplate data.
For V/f and VVW controls the setting range goes up to 300 Hz.
For vector control the setting range is from 30 Hz to 120 Hz.
P0404 – Motor Rated Power
Adjustable
Range:
)
Factory
Setting:
Motor
max-ND
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
43 Motor Data
Description:
Set it according to the used motor nameplate data.
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...