Digital and Analog Inputs and Outputs
Description:
These parameters set the functions of the analog outputs, according to the
.
Table 13.3 -
Analog output functions
Functions
P0251
(AO1)
P0254
(AO2)
P0257
(AO3)
P0260
(AO4)
Speed Reference
0
0
0
0
Total Reference
1
1
1
1
Real Speed
2*
2
2*
2
Torque Current Reference (Vector Mode)
3
3
3
3
Torque Current (Vector Mode)
4
4
4
4
Output Current (with a 0.3 second filter)
5
5*
5
5*
PID Process Variable
6
6
6
6
Active Current (V/f or VVW Mode, with a 0.1 second filter)
7
7
7
7
Output Power (with a 0.5 second filter)
8
8
8
8
PID Setpoint
9
9
9
9
Torque Current > 0 (Vector Mode)
10
10
10
10
Motor Torque
11
11
11
11
SoftPLC
12
12
12
12
PTC
13
13
-
-
Not Used
14 and 15
14 and 15
13, 14, 15
and 22
13, 14, 15
and 22
Motor Ixt
16
16
16
16
Encoder Speed
17
17
17
17
P0696 Value
18
18
18
18
P0697 Value
19
19
19
19
P0698 Value
20
20
20
20
P0699 Value
21
21
21
21
PLC11
22
22
-
-
Id* Current
23
23
23
23
Exclusive WEG Use
-
-
24 to 71
24 to 71
* Factory Setting
P0252 – AO1 Gain
P0255 – AO2 Gain
P0258 – AO3 Gain
P0261 – AO4 Gain
Adjustable
Range:
0.000 to 9.999
Factory
Setting:
1.000
Properties:
Access groups
via HMI:
07 I/O CONFIGURATION
or
01 PARAMETER GROUPS
39 Analog Outputs
39 Analog Outputs
Description:
They adjust the analog output gains. Refer to the
.
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...