Scalar Control (V/f)
9-12
9
DC Link Voltage (P0004)
F022-Overvoltage
Time
DC Link Regulation
Output Speed
Time
P0151
Nominal U
d
Figure 9.13 -
Example of the DC link voltage limitation working with the Ramp Acceleration function
P0150 – DC Regulator Type (V/f)
Adjustable
Range:
0 = Ramp Hold
1 = Ramp Acceleration
Factory
Setting:
0
Properties:
V/f, CFG and VVW
Access groups
via HMI:
01 PARAMETER GROUPS
27 V/f DC Volt. Limit.
Description:
It selects the DC link voltage limitation function type in the V/f mode.
P0151 – DC Link Voltage Regulation Acting Level (V/f)
Adjustable
Range:
339 to 400 V (P0296 = 0)
585 to 800 V (P0296 = 1)
585 to 800 V (P0296 = 2)
585 to 800 V (P0296 = 3)
585 to 800 V (P0296 = 4)
809 to 1000 V (P0296 = 5)
809 to 1000 V (P0296 = 6)
924 to 1200 V (P0296 = 7)
924 to 1200 V (P0296 = 8)
Factory
Setting:
400 V
800 V
800 V
800 V
800 V
1000 V
1000 V
1000 V
1200 V
Properties:
V/f and VVW
Access groups
via HMI:
01 PARAMETER GROUPS
27 V/f DC Volt. Limit.