VVW Control
10-4
10
P0400 – Motor Rated Voltage
P0401 – Motor Rated Current
P0402 – Motor Rated Speed
P0403 – Motor Rated Frequency
P0404 – Motor Rated Power
P0406 – Motor Ventilation
Refer to the
Section 11.7 MOTOR DATA [43] on page 11-10
, for more information.
P0407 – Motor Rated Power Factor
Adjustable
Range:
0.50 to 0.99
Factory
Setting:
0.68
Properties:
CFG and VVW
Access groups
via HMI:
01 PARAMETER GROUPS
43 Motor Data
Description:
It is the motor power factor setting, according to the motor nameplate data (cos Ø).
This parameter is important for the VVW control operation. The inaccurate setting will imply in incorrect calculation
of the slip compensation.
The default value of this parameter is adjusted automatically when the parameter P0404 is changed. The suggested
value is valid for three-phase, IV pole WEG motors. For other motor types the setting must be done manually.
P0408– Run Self-Tuning
P0409 – Motor Stator Resistance (Rs)
P0410 – Motor Magnetizing Current (I
m
)
Refer to the
Item 11.8.5 Self-Tuning [05] and [94] on page 11-23
, for more information.
10.3 VVW CONTROL MODE START-UP
NOTA!
Read the whole CFW-11 user's manual before installing, powering or operating the inverter.
Sequence for installation, verification, powering and start-up:
a)
Install the inverter:
according to the chapter 3 - Installation and Connection, of the CFW-11 user's manual,
wiring all the power and control connections.
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...