12-23
12
Functions Common to All the Control Modes
Description:
This parameter adjusts the current level (DC braking torque) applied to the motor during the braking.
The programmed current level is a percentage of the inverter rated current.
This parameter works only in the Sensorless Vector control mode.
12.9 SKIP SPEED [48]
The parameters of this group prevent the motor from operating permanently at speed values where, for instance,
the mechanic system enters in resonance (causing exaggerated vibration or noise).
P0303 – Skip Speed 1
Adjustable
Range:
0 to 18000 rpm
Factory
Setting:
600 rpm
P0304 – Skip Speed 2
Adjustable
Range:
0 to 18000 rpm
Factory
Setting:
900 rpm
P0305 – Skip Speed 3
Adjustable
Range:
0 to 18000 rpm
Factory
Setting:
1200 rpm
P0306 – Skip Band
Adjustable
Range:
0 to 750 rpm
Factory
Setting:
0 rpm
Properties:
Access groups
via HMI:
01 PARAMETER GROUPS
48 Skip Speed
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...