PM Vector Control
21-18
21
21.9 FAULTS AND ALARMS
When the control mode is PM with encoder (P0202 = 6), fault reset will only be accepted with stopped motor.
Except for the F079 (Encoder fault) reset, which could occur with the motor shaft in movement; however, the
motor must be stopped in order to avoid operation problems after the fault reset.
21.10 READ-ONLY PARAMETERS [09]
P0009 – Motor Torque
Adjustable
Range:
-1000.0 to 1000.0 %
Factory
Setting:
Properties:
RO
Access groups
via HMI:
09 READ ONLY PARAMETERS
Description:
It indicates the torque developed by the motor, as a percentage of the motor rated current (P0401). By using the
analog output AO1 or AO2 (modulus), AO3 or AO4 programmed to show the torque current reference (Iq*), the
motor torque can be calculated through the following formula:
T
motor
= {Iq* x P0401 x 20 [%]} / I
HD
Where:
Iq
* in (Volts).
I
HD
is the inverter HD current (P0295).
21.11 SPEED LIMITS
P0134 - Maximum Speed Reference Limit
Parameters related to the motor:
The maximum allowed speed is automatically set in the value defined by:
P0134
limit
= Ud
max.
X 636 / P0435.
Table 21.2 -
Maximum dc link voltage
P0296
220/240 V
380 V...480 V
500 V...600 V
660/690 V
Ud
máx.
400 V
800 V
1000 V
1200 V
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...