Functions Common to All the Control Modes
12-2
12
open
open
24V
Time
24V
Time
P0102
P0100
DIx -
Run/Stop
2
nd
ramp DIx
Motor Speed
P0103
P0101
Time
Figure 12.1 -
Second ramp actuation
In this example, the commutation to the 2nd ramp (P0102 or P0103) is done by means of one of the digital inputs
from DI1 to DI8, provided that it had been programmed for 2nd ramp function (refer to the
, for more details).
Note:
The setting 0.0 s means that the ramp is disabled.
P0104 – S Ramp
Adjustable
Range:
0 = Off
1 = 50 %
2 = 100 %
Factory
Setting:
0
Properties:
Access groups
via HMI:
01 PARAMETER GROUPS
20 Ramps
Description:
This parameter allows that the acceleration and deceleration ramps have a nonlinear profile, similar to an "S", as
showed in the
next.
Deceleration Time
(P0101/P0103)
Acceleration
Time(P0100/P0102)
t (s)
100 % S ramp
50 % S ramp
Linear
Speed
Figure 12.2 -
S or linear ramp
The S ramp reduces mechanic shock during accelerations/decelerations.
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...