Starting-up and Settings
7-4
7
NOTE!
Valid for P0318 = 1.
When the inverter is powered and the memory module is present, the current parameter contents
are compared with the contents of the parameters saved in the MMF and, in case they are different,
the keypad (HMI) will exhibit the message "Flash Mem.Module with different parameters", after 3
seconds the message is replaced by the parameter P0318 menu. The user has the option to overwrite
the contents of the memory module (choosing P0318 = 1), or overwrite the inverter parameters
(choosing P0318 = 2), or even ignore the message by programming P0318 = 0.
NOTE!
When using the network communication board, the SoftPLC function or the PLC11 board, it is
recommended to set the parameter P0318 = 0.x
P0319 – Copy Function HMI
Adjustable
Range:
0 = Off
1 = VFD
→
HMI
2 = HMI
→
VFD
Factory
Setting:
0
Properties:
CFG
Access groups
via HMI:
06 BACKUP PARAMETERS
Description:
The Copy Function HMI is similar to the previous, and it is also used to transfer the contents of the parameters
from one inverter to another (others). The inverters have the same software version. If the versions are different, by
programming P0319 = 2, the HMI will show the message "Incompatible software version" during 3 seconds. After
removing the message from the HMI, the content of P0319 returns to zero.
Table 7.3 -
Parameter P0319 options
P0319
Action
0
Inactive:
no action
1
Inverter
→
HMI:
transfers the inverter current parameters and the user memories 1, 2 and 3 contents to the keypad (HMI)
nonvolatile memory (EEPROM). The inverter current parameters remain unchanged
(1)
2
HMI
→
Inverter:
transfers the content of the keypad (HMI) nonvolatile memory (EEPROM) to the current inverter parameters
and to the user memories 1, 2 and 3. After the transfer has been finished, an inverter reset occurs
(1)
(1)
The content of P0319 returns to zero.
NOTE!
In case the keypad (HMI) had been previously loaded with parameters from a version "different"
from that of the inverter where one is trying to copy the parameters, the operation will not be
carried out and the keypad (HMI) will indicate the fault F082 (Copy Function Fault). It is understood
as "different" versions, those that differ in the "x" and "y" digits, assuming that the software version
numbers be described as Vx.yz.
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...