Trace Function [52]
19-2
19
Description:
It defines the value for comparison with the variable selected in P0550.
The full range of the variables selectable as trigger is presented in the next table.
Table 19.1 -
Full scale of the variables selectable as trigger
Variable
Full Scale
Speed Reference
100 % = P0134
Motor Speed
100 % = P0134
Motor Current
200 % = 2.0 x I
nomHD
DC Link Voltage
100 % = Max. Lim. P0151
Motor Frequency
340 % = 3.4 x P0403
Motor Voltage
100 % =1.0 x P0400
Motor Torque
200 % = 2.0 x I
nom Motor
Process Variable
100 % = 1.0 x P0528
PID Setpoint
100 % = 1.0 x P0528
AI1
100 % = 10 V/20 mA
AI2
100 % = 10 V/20 mA
AI3
100 % = 10 V/20 mA
AI4
100 % = 10 V/20 mA
This parameter has no effect when P0552 = "Alarm", "Fault" or "DIx".
P0552 – Trigger Condition for Trace
Adjustable
Range:
0: P0550* = P0551
1: P0550* <> P0551
2: P0550* > P0551
3: P0550* < P0551
4: Alarm
5: Fault
6: DIx
Factory
Setting:
5
Properties:
Access groups
via HMI:
01 PARAMETER GROUPS
52 Trace Function
Description:
It defines the condition for starting the signal acquisition. The
details the available options.
Table 19.2 -
Parameter P0552 option description
P0552 Options
Description
P0550* = P0551
The variable selected in P0550 is equal to the value adjusted in P0551
P0550* ≠ P0551
The variable selected in P0550 is different from the value adjusted in P0551
P0550* > P0551
The variable selected in P0550 is bigger than the value adjusted in P0551
P0550* < P0551
The variable selected in P0550 is smaller than the value adjusted in P0551
Alarm
Inverter with an active alarm
Fault
Inverter in fault state
DIx
Digital input (selected via P0263 – P0270)
For P0552=6 ("DIx" option), it is necessary to select the option "Trace Function" at one of the parameters from P0263
to P0270. For more details, refer to the
Item 13.1.3 Digital Inputs [40] on page 13-12
.
Notes:
- If P0552 = 6 and no DI is configured for "Trace Function", the trigger will not occur.
- If P0552 = 6 and several DIs were configured for "Trace Function", only one has to be active for the trigger
occurrence.
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...