13-27
13
Digital and Analog Inputs and Outputs
P0287 – Hysteresis for Nx and Ny
Adjustable
Range:
0 to 900 rpm
Factory
Setting:
18 rpm
(15 rpm)
Properties:
Access groups
via HMI:
07 I/O CONFIGURATION
or
01 PARAMETER GROUPS
41 Digital Outputs
41 Digital Outputs
Description:
It is used in the
N > Nx
and
N < Ny
functions of the digital and relay outputs.
P0288 – Nx Speed
Adjustable
Range:
0 to 18000 rpm
Factory
Setting:
120 rpm
(100 rpm)
P0289 – Ny Speed
Adjustable
Range:
0 to 18000 rpm
Factory
Setting:
1800 rpm
(1500 rpm)
Properties:
Access groups
via HMI:
07 I/O CONFIGURATION
or
01 PARAMETER GROUPS
41 Digital Outputs
41 Digital Outputs
Description:
They are used in the
N* > Nx, N > Nx,
and
N < Ny
functions of the digital and relay outputs.
P0290 – Ix Current
Adjustable
Range:
0 to 2 x I
nom-ND
Factory
Setting:
1.0 x I
nom-ND
Properties:
Access groups
via HMI:
07 I/O CONFIGURATION
or
01 PARAMETER GROUPS
41 Digital Outputs
41 Digital Outputs
Description:
It is used in the
Is > Ix
and
Ix < Ix
functions of the digital and relay outputs.
P0291 – Zero Speed Zone
Adjustable
Range:
0 to 18000 rpm
Factory
Setting:
18 rpm
(15 rpm)
Properties:
Access groups
via HMI:
07 I/O CONFIGURATION
or
01 PARAMETER GROUPS
35 Zero Speed Logic
41 Digital Outputs
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...