Quick Parameter Reference, Faults and Alarms
0-7
0
Parameter
Function
Adjustable Range
Factory Setting
User
Setting
Properties
Groups
Pag.
P0220
LOC/REM Selection Src
0 = Always LOC
1 = Always REM
2 = LR Key LOC
3 = LR Key REM
4 = DIx
5 = Serial/USB LOC
6 = Serial/USB REM
7 = Anybus-CC LOC
8 = Anybus-CC REM
9 = CO/DN/DP LOC
10 = CO/DN/DP REM
11 = SoftPLC LOC
12 = SoftPLC REM
13 = PLC11 LOC
14 = PLC11 REM
2
CFG
31, 32, 33,
110
P0221
LOC Reference Sel.
0 = HMI
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = Sum AIs > 0
6 = Sum AIs
7 = E.P.
8 = Multispeed
9 = Serial/USB
10 = Anybus-CC
11 = CANop/DNet/DP
12 = SoftPLC
13 = PLC11
0
CFG
31, 36, 37,
38, 110
P0222
REM Reference Sel.
See options in P0221
1
CFG
32, 36, 37,
38, 110
P0223
LOC FWD/REV Selection
0 = Always FWD
1 = Always REV
2 = FR Key FWD
3 = FR Key REV
4 = DIx
5 = Serial/USB FWD
6 = Serial/USB REV
7 = Anybus-CC FWD
8 = Anybus-CC REV
9 = CO/DN/DP FWD
10 = CO/DN/DP REV
11 = AI4 Polarity
12 = SoftPLC FWD
13 = SoftPLC REV
14 = AI2 Polarity
15 = PLC11 FWD
16 = PLC11 REV
2
CFG, V/f,
VVW and
Vector
31, 33, 110
P0224
LOC Run/Stop Sel.
0 = I,O Keys
1 = DIx
2 = Serial/USB
3 = Anybus-CC
4 = CANop/DNet/DP
5 = SoftPLC
6 = PLC11
0
CFG
31, 33, 110
P0225
LOC JOG Selection
0 = Disable
1 = JOG Key
2 = DIx
3 = Serial/USB
4 = Anybus-CC
5 = CANop/DNet/DP
6 = SoftPLC
7 = PLC11
1
CFG
31, 110
P0226
REM FWD/REV Sel.
See options in P0223
4
CFG, V/f,
VVW and
Vector
32, 33, 110
P0227
REM Run/Stop Sel.
See options in P0224
1
CFG
32, 33, 110
P0228
REM JOG Selection
See options in P0225
2
CFG
32, 110
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...