13-31
13
Digital and Analog Inputs and Outputs
P0224 – Run/Stop Selection – LOCAL Situation
P0227 – Run/Stop Selection - REMOTE Situation
Adjustable
Range:
0 = Keys
,
1 = DIx
2 = Serial/USB
3 = Anybus-CC
4 = CANopen/DeviceNet/Profibus DP
5 = SoftPLC
6 = PLC11
Factory
Setting:
P0224 = 0
P0227 = 1
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
or
01 PARAMETER GROUPS
31 Local Command
32 Remote Command
Description:
They define the origin of the Run/Stop command in the LOCAL situation and in the REMOTE situation.
P0225 – JOG Selection – LOCAL Situation
P0228 – JOG Selection - REMOTE Situation
Adjustable
Range:
0 = Disabled
1 = JOG Key
2 = DIx
3 = Serial/USB
4 = Anybus-CC
5 = CANopen/DeviceNet/Profibus DP
6 = SoftPLC
7 = PLC11
Factory
Setting:
P0225 = 1
P0228 = 2
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
or
01 PARAMETER GROUPS
31 Local Command
32 Remote Command
Description:
They define the origin of the JOG command in the LOCAL situation and in the REMOTE situation.
P0229 – Stop Mode Selection
Adjustable
Range:
0 = Ramp to Stop
1 = Coast to Stop
2 = Fast Stop
3 = By Ramp with Iq*
4 = Fast Stop with Iq*
Factory
Setting:
0
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
or
01 PARAMETER GROUPS
31 Local Command
32 Remote Command
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...