175
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Inverter
Parameters
User 1
P204 = 10
P265 to P269 (DIx) = 20
DIx = 24 V
DIx = 0 V
DIx = 24 V
- The functions
JOG+
and
JOG –
are valid only for P202 = 3 and 4.
- The option
Fieldbus
sets the DI as a remote input for the Fieldbus system
and in order to become effective it must be read as any other
DI of the inverter.
Disable Flying Start
: Put +24 V at the digital input to disable Flying
Start.
- The function
Loads user via DIx
, permits the memory selection of the
user 1 or 2, process similar to P204 = 7 and P204 = 8, but the user is
loaded from the transition of a DIx programmed for this function.
The memory of user 1 is loaded, when the DIx status changes from low
level to high level (transition from 0 V to 24 V) and P265 to P269 = 20,
provided the current parameter contents of the inverter have been
transferred previously to the parameter memory 1 (P204 = 10).
The memory of user 2 is loaded, when the DIx status changes from high
level to low level (transition from 24 V to 0 V) and P265 to P269 = 20,
provided the current parameter contents of the inverter have been
transferred previously to the parameter memory 2 (P204 = 11).
User 2
P204 = 11
DIx = 0 V
P265 to P269 (DIx) = 20
Figure 6.35
- Details about the operation of the function load user via DIx
NOTE!
Ensure that when using this function, the parameter sets (User
Memory 1 and 2) are totally compatible with the used installations
(motors, ON/OFF commands, etc.).
User memory cannot be loaded when motor is enabled.
When two different motor parameter sets are saved into the User
Memory 1 and 2, respectively, set for each user the correct values
at the Parameters P156, P157 and P158.
When the function
'Parameter Setting Disable'
is programmed and
the DIx input is +24 V, the parameters cannot be changed, independent
of the values that have been set at P000 and P200. When the Dix input
is set to 0 V, the parameter changing will be conditioned to the values
set at P000 and P200.