CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
The parameters P295 (Inverter Rated Current), P296 (Inverter Rated
Voltage), P297 (Switching Frequency), P308 (Serial Address) and P201
(Language) are not changed when the factory default parameters are
loaded through P204 = 5 and 6.
In order to load the User Parameters #1 (P204 = 7) and/or the User
Parameters #2 (P204 = 8) into the operation area of the CFW-09, it is
necessary that the User Memory #1 and/or the User Memory #2 have
been previously saved (P204 = 10 and/or P204 = 11).
Once entered the user parameters are automatically saved to the VSD
EEPROM. In addition it is possible to save two further sets of
parameters, or to use these as a “backup”.
The operation of Load User 1 and/or 2 can also be done by DIx (refer to
parameters P265 to P269).
The options P204 = 5, 6, 7, 8, 10 and 11 are disables when P309
0
(Active Fieldbus).
P204
(1)(10)
0 to 11
Load/Save
[ 0 ]
Parameters
-
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Current
Inverter
Parameters
Factory
Default
User
Default
1
User
Default
2
P204 = 5
or 6
Figure 6.23
- Parameter transference