139
No. Function to the associated setting
2 M2: Heating circuit with mixer – control mode
M3: Heating circuit with mixer – moves into the CLOSE position
No heat pump blocking
3 M2/M3: Heating circuits with mixer – move into the CLOSE position
No heat pump blocking
4 M2/M3: Heating circuits with mixer – control mode
Heat pump blocking
5 M2: Heating circuit with mixer – moves into the CLOSE position
M3: Heating circuit with mixer – control mode
Heat pump blocking
6 M2: Heating circuit with mixer – control mode
M3: Heating circuit with mixer – moves into the CLOSE position
Heat pump blocking
7 M2/M3: Heating circuits with mixer – move into the CLOSE position
Heat pump blocking
8 Blocking of cooling with AC-Box
M2/M3: Heating circuits with mixer – control mode
Heat pump blocking
Type Vitosolic
Parameter
■ 7016
Determination which type of Vitosolic
(100 or 200) is installed in the system.
Access
■ "
Device settings
"
■ "
Programming
"
■ "
System definition
"
■
y
to
"Vitosolic type"
■
l
or
m
Standard setting
0
Setting range
0 to 2
Settings explained:
0 No solar control unit Vitosolic
1 Vitosolic 100
2 Vitosolic 200
System definition control settings
External Blocking/mixer CLOSE
(cont.)
5368 522 UAE